Your current location:home > Product

Your current location:home > News > News Details

Supply and demand

Direct combustion pressure regulator box

2 Brief introduction:
In china,we use direct combustion equipments. For instance, gas fired boiler, gas air conditioner and gas burner are all used with low pressure of 50-100mbar. And those are using low pressure of 50-150mbar. Knowing this kind of equipment’s feature, our company has already developed a series of high quality direct combustion pressure regulating boxes. These products are designed for industrial gas, the flow rate shocks, open and shut promptly and uninterrupted gas supply. It owns many functions such as filter, voltage regulation and computation. It also can reflect rapidly, steady outlet pressure and highly closed precision under the condition of the unpredictable change for the range of flow to meet the needs of industrial and civilian use.

  调压箱-亚威系列
       
       
  调压箱-亚威系列

2 Features:

  • The major components of regulator are the major regulator, limiting pressure closing system, flow meter and meter control. Those are premium brands to guarantee its high quality, high degree of accuracy and high reliability
  • The pressure regulating box owns a high accuracy degree of filter (5μm). Users can change the filter timely for differential manometer can reflect how dirty the filter element is.
  • The regulator is furnished with limiting pressure closing system. When loses control, it can disconnect air supply automatically to ensure the steady of the manometer.
  • We can regulate the manometer both artificial and automatic method to make sure the instantly air supply
  • It experienced strict pressure-tight and gas-tight test to ensure the system of no leakage.
 
       
 
The main technical parameters

Regulator’Mode

YWH-200A/B

YWH-300A/B

YWH-600A/B

YWH-1000A/B

YWH-2000A/B

YWH-3000A/B

Main regulator

A109

A149

MBN/40

MBN/50

MBN/80-BP

MBN/100-BP

RTZ-SL

133L

133L

133L

133L

RTJ-N

Entrance pressure’s range(Mpa)

0.1-0.5

0.1-0.5

0.1-0.5

0.1-0.5

0.1-0.5

0.1-0.5

Exit pressure’s range(Kpa)

2.4

2.4

2.4

2.4

2.4

2.4

Maximum flow(NG Nm3/h)

≥200

300-400

500-800

900-1000

2000-2800

300-4000

Entrance caliber

DN50
PN1.6

DN50
PN1.6

DN65
PN1.6

DN80
PN1.6

DN125
PN1.6

DN150
PN1.6

Exit caliber

DN50
PN1.6

DN65
PN1.6

DN100
PN1.6

DN125
PN1.6

DN200
PN1.6

DN200
PN1.6

Entrance/Exit central distance
(mm)d

A

850

810

900

930

2070

2050

B

850

810

900

930

2070

2050

Size of the box
(mm)
a×b×c

A

1300×1000×1130

1300×1000×1280

1500×1200×1850

1550×1200×1900

2700×1460×2200

2730×1650×2310

B

1300×550×1130

1300×550×1180

1450×750×1600

1650×850×1600

2700×960×1800

2730×1060×1800

Regulating precision(δP2)

≤±5%

Closing precision

≤10%

Working temperature

-20℃ - +60℃

Applied medium

City gas、LPG、Mixed gas、NG and Noncorrosivegas.

 